ZONEHVAC:IDEALLOADSAIRSYSTEM
Ideal system used to calculate loads without modeling a full HVAC system. All that is required for the ideal system are zone controls, zone equipment configurations, and the ideal loads system component. This component can be thought of as an ideal unit that mixes zone air with the specified amount of outdoor air and then adds or removes heat and moisture at 100% efficiency in order to meet the specified controls. Energy use is reported as DistrictHeating and DistrictCooling.
Name
Availability Schedule Name
Type: list of objects
(
SCHEDULE:COMPACT,
SCHEDULE:FILE,
SCHEDULE:CONSTANT,
EXTERNALINTERFACE:SCHEDULE,
EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE or
SCHEDULE:YEAR)
Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Zone Supply Air Node Name
Type: node
Must match a zone air inlet node name.
Zone Exhaust Air Node Name
Type: node
Should match a zone air exhaust node name. This field is optional, but is required if this this object is used with other forced air equipment.
System Inlet Air Node Name
Type: node
This field is only required when the Ideal Loads Air System is connected to an AirloopHVAC:ZoneReturnPlenum, otherwise leave this field blank. When connected to a plenum the return plenum Outlet Node Name (or Induced Air Outlet Node Name when connecting multiple ideal loads air sytems) is entered here. The two ideal loads air system node name fields described above, the Zone Supply Air Node Name and the Zone Exhaust Air Node Name must also be entered. The Zone Supply Air Node Name must match a zone inlet air node name for the zone where this Ideal Loads Air System is connected. The Zone Exhaust Air Node Name must match an inlet air node name of an AirloopHVAC:ReturnAirPlenum object.
Maximum Heating Supply Air Temperature
Unit: C
Default: 50
Minimum Cooling Supply Air Temperature
Unit: C
Default: 13
Maximum Heating Supply Air Humidity Ratio
Unit: kgWater/kgDryAir
Default: 0.0156
Minimum Cooling Supply Air Humidity Ratio
Unit: kgWater/kgDryAir
Default: 0.0077
Heating Limit
Type: choice
(NoLimit, LimitFlowRate, LimitCapacity or LimitFlowRateAndCapacity)
Default: NoLimit
Maximum Heating Air Flow Rate
This field is ignored if Heating Limit = NoLimit If this field is blank, there is no limit.
Unit: m3/s
Minimum: 0.0
Maximum Sensible Heating Capacity
This field is ignored if Heating Limit = NoLimit If this field is blank, there is no limit.
Unit: W
Minimum: 0.0
Cooling Limit
Type: choice
(NoLimit, LimitFlowRate, LimitCapacity or LimitFlowRateAndCapacity)
Default: NoLimit
Maximum Cooling Air Flow Rate
This field is ignored if Cooling Limit = NoLimit This field is required if Outdoor Air Economizer Type is anything other than NoEconomizer.
Unit: m3/s
Minimum: 0.0
Maximum Total Cooling Capacity
This field is ignored if Cooling Limit = NoLimit
Unit: W
Minimum: 0.0
Heating Availability Schedule Name
Type: list of objects
(
SCHEDULE:COMPACT,
SCHEDULE:FILE,
SCHEDULE:CONSTANT,
EXTERNALINTERFACE:SCHEDULE,
EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE or
SCHEDULE:YEAR)
If blank, heating is always available.
Cooling Availability Schedule Name
Type: list of objects
(
SCHEDULE:COMPACT,
SCHEDULE:FILE,
SCHEDULE:CONSTANT,
EXTERNALINTERFACE:SCHEDULE,
EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE or
SCHEDULE:YEAR)
If blank, cooling is always available.
Dehumidification Control Type
Type: choice
(ConstantSensibleHeatRatio, Humidistat, None or ConstantSupplyHumidityRatio)
ConstantSensibleHeatRatio means that the ideal loads system will be controlled to meet the sensible cooling load, and the latent cooling rate will be computed using a constant sensible heat ratio (SHR) Humidistat means that there is a ZoneControl:Humidistat for this zone and the ideal loads system will attempt to satisfy the humidistat. None means that there is no dehumidification. ConstantSupplyHumidityRatio means that during cooling the supply air will always be at the Minimum Cooling Supply Humidity Ratio.
Default: ConstantSensibleHeatRatio
Cooling Sensible Heat Ratio
This field is applicable only when Dehumidification Control Type is ConstantSensibleHeatRatio
Unit: dimensionless
Maximum: 1.0
Default: 0.7
Humidification Control Type
Type: choice
(None, Humidistat or ConstantSupplyHumidityRatio)
None means that there is no humidification. Humidistat means that there is a ZoneControl:Humidistat for this zone and the ideal loads system will attempt to satisfy the humidistat. ConstantSupplyHumidityRatio means that during heating the supply air will always be at the Maximum Heating Supply Humidity Ratio.
Default: None
Design Specification Outdoor Air Object Name
Type: list of objects
( or
DESIGNSPECIFICATION:OUTDOORAIR)
When the name of a DesignSpecification:OutdoorAir object is entered, the minimum outdoor air flow rate will be computed using these specifications. The outdoor air flow rate will also be affected by the next two fields. If this field is blank, there will be no outdoor air and the remaining fields will be ignored.
Outdoor Air Inlet Node Name
Type: node
This field is required if the system provides outdoor air Enter the name of an outdoor air node. This node name is also specified in an OutdoorAir:Node or OutdoorAir:NodeList object.
Demand Controlled Ventilation Type
Type: choice
(None, OccupancySchedule or CO2Setpoint)
This field controls how the minimum outdoor air flow rate is calculated. None means that design occupancy will be used to compute the minimum outdoor air flow rate OccupancySchedule means that current occupancy level will be used. CO2Setpoint means that the design occupancy will be used to compute the minimum outdoor air flow rate and the outdoor air flow rate may be increased if necessary to maintain the indoor air carbon dioxide setpoint defined in a ZoneControl:ContaminantController object.
Default: None
Outdoor Air Economizer Type
Type: choice
(NoEconomizer, DifferentialDryBulb or DifferentialEnthalpy)
DifferentialDryBulb and DifferentialEnthalpy will increase the outdoor air flow rate when there is a cooling load and the outdoor air temperature or enthalpy is below the zone exhaust air temperature or enthalpy.
Default: NoEconomizer
Heat Recovery Type
Type: choice
(None, Sensible or Enthalpy)
Default: None
Sensible Heat Recovery Effectiveness
Unit: dimensionless
Minimum: 0.0
Maximum: 1.0
Default: 0.70
Latent Heat Recovery Effectiveness
Applicable only if Heat Recovery Type is Enthalpy.
Unit: dimensionless
Minimum: 0.0
Maximum: 1.0
Default: 0.65
Design Specification ZoneHVAC Sizing Object Name
Type: list of objects
( or
DESIGNSPECIFICATION:ZONEHVAC:SIZING)
Enter the name of a DesignSpecificationZoneHVACSizing object.