ZONE

Defines a thermal zone of the building.

Name
Type: alphanumeric

Direction of Relative North
Type: real number
Unit: deg
Default: 0
Values in example files: 0.0 deg in 773 files, -36.87 deg in 1 file, 180.0 deg in 2 files, 36.87 deg in 1 file
X Origin
Type: real number
Unit: m
Default: 0
Values in example files: from -64.0 m to 201.98 m

Y Origin
Type: real number
Unit: m
Default: 0
Values in example files: from 0.0 m to 131.674 m

Z Origin
Type: real number
Unit: m
Default: 0
Values in example files: from -2.439 m to 33.5366 m

Type
Type: integer
Minimum: 1
Maximum: 1
Default: 1

Multiplier
Type: integer
Minimum: 1
Default: 1

Ceiling Height
Type: real number
If this field is 0.0, negative or autocalculate, then the average height of the zone is automatically calculated and used in subsequent calculations. If this field is positive, then the number entered here will be used. Note that the Zone Ceiling Height is the distance from the Floor to the Ceiling in the Zone, not an absolute height from the ground.
Unit: m
Default: autocalculate
Values in example files: from -9999.0 m to 5.0088 m

Volume
Type: real number
If this field is 0.0, negative or autocalculate, then the volume of the zone is automatically calculated and used in subsequent calculations. If this field is positive, then the number entered here will be used.
Unit: m3
Default: autocalculate
Values in example files: from 0.0 m3 to 5605.3198 m3

Floor Area
Type: real number
If this field is 0.0, negative or autocalculate, then the floor area of the zone is automatically calculated and used in subsequent calculations. If this field is positive, then the number entered here will be used.
Unit: m2
Default: autocalculate
Values in example files: empty in 169 files, autocalculate m2 in 608 files
Zone Inside Convection Algorithm
Type: choice (Simple, TARP, CeilingDiffuser, AdaptiveConvectionAlgorithm or TrombeWall)
Will default to same value as SurfaceConvectionAlgorithm:Inside object setting this field overrides the default SurfaceConvectionAlgorithm:Inside for this zone Simple = constant natural convection (ASHRAE) TARP = variable natural convection based on temperature difference (ASHRAE) CeilingDiffuser = ACH based forced and mixed convection correlations for ceiling diffuser configuration with simple natural convection limit AdaptiveConvectionAlgorithm = dynamic selection of convection models based on conditions TrombeWall = variable natural convection in an enclosed rectangular cavity

Zone Outside Convection Algorithm
Type: choice (SimpleCombined, TARP, DOE-2, MoWiTT or AdaptiveConvectionAlgorithm)
Will default to same value as SurfaceConvectionAlgorithm:Outside object setting this field overrides the default SurfaceConvectionAlgorithm:Outside for this zone SimpleCombined = Combined radiation and convection coefficient using simple ASHRAE model TARP = correlation from models developed by ASHRAE, Walton, and Sparrow et. al. MoWiTT = correlation from measurements by Klems and Yazdanian for smooth surfaces DOE-2 = correlation from measurements by Klems and Yazdanian for rough surfaces AdaptiveConvectionAlgorithm = dynamic selection of correlations based on conditions

Part of Total Floor Area
Type: choice (Yes or No)
Default: Yes