WATERHEATER:STRATIFIED
Water heater with stratified, multi-node water tank. May be used to model a tankless water heater (small tank volume), a hot water storage tank (zero heater capacity), or a heat pump water heater (see WaterHeater:HeatPump:*.)
Name
Type: alphanumeric
End-Use Subcategory
Type: alphanumeric
Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
Default: General
Tank Volume
Type: real number
Unit: m3
Tank Height
Type: real number
Height is measured in the axial direction for horizontal cylinders
Unit: m
Tank Shape
Type: choice
(VerticalCylinder, HorizontalCylinder or Other)
Default: VerticalCylinder
Tank Perimeter
Type: real number
Only used if Tank Shape is Other
Unit: m
Minimum: 0.0
Maximum Temperature Limit
Type: real number
Unit: C
Heater Priority Control
Type: choice
(MasterSlave or Simultaneous)
Default: MasterSlave
Heater 1 Setpoint Temperature Schedule Name
Type: list of objects
(
SCHEDULE:COMPACT,
SCHEDULE:FILE,
SCHEDULE:YEAR,
SCHEDULE:CONSTANT,
EXTERNALINTERFACE:SCHEDULE or
EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE)
Heater 1 Deadband Temperature Difference
Type: real number
Unit: deltaC
Minimum: 0.0
Default: 0.0
Heater 1 Capacity
Type: real number
Unit: W
Minimum: 0.0
Heater 1 Height
Type: real number
Unit: m
Minimum: 0.0
Heater 2 Setpoint Temperature Schedule Name
Type: list of objects
(
SCHEDULE:COMPACT,
SCHEDULE:FILE,
SCHEDULE:YEAR,
SCHEDULE:CONSTANT,
EXTERNALINTERFACE:SCHEDULE or
EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE)
Heater 2 Deadband Temperature Difference
Type: real number
Unit: deltaC
Minimum: 0.0
Default: 0.0
Heater 2 Capacity
Type: real number
Unit: W
Minimum: 0.0
Heater 2 Height
Type: real number
Unit: m
Minimum: 0.0
Heater Fuel Type
Type: choice
(Electricity, NaturalGas, Propane, FuelOilNo1, FuelOilNo2, Coal, Diesel, Gasoline, OtherFuel1, OtherFuel2, Steam or DistrictHeating)
Heater Thermal Efficiency
Type: real number
Maximum: 1.0
Off Cycle Parasitic Fuel Consumption Rate
Type: real number
Unit: W
Minimum: 0.0
Default: 0.0
Off Cycle Parasitic Fuel Type
Type: choice
(Electricity, NaturalGas, Propane, FuelOilNo1, FuelOilNo2, Coal, Diesel, Gasoline, OtherFuel1, OtherFuel2, Steam or DistrictHeating)
Off Cycle Parasitic Heat Fraction to Tank
Type: real number
Minimum: 0.0
Maximum: 1.0
Default: 0.0
Off Cycle Parasitic Height
Type: real number
Unit: m
Minimum: 0.0
Default: 0.0
On Cycle Parasitic Fuel Consumption Rate
Type: real number
Unit: W
Minimum: 0.0
Default: 0.0
On Cycle Parasitic Fuel Type
Type: choice
(Electricity, NaturalGas, Propane, FuelOilNo1, FuelOilNo2, Coal, Diesel, Gasoline, OtherFuel1, OtherFuel2, Steam or DistrictHeating)
On Cycle Parasitic Heat Fraction to Tank
Type: real number
Minimum: 0.0
Maximum: 1.0
Default: 0.0
On Cycle Parasitic Height
Type: real number
Unit: m
Minimum: 0.0
Default: 0.0
Ambient Temperature Indicator
Type: choice
(Schedule, Zone or Outdoors)
Ambient Temperature Schedule Name
Type: list of objects
(
SCHEDULE:COMPACT,
SCHEDULE:FILE,
SCHEDULE:YEAR,
SCHEDULE:CONSTANT,
EXTERNALINTERFACE:SCHEDULE or
EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE)
Ambient Temperature Zone Name
Type: list of objects
( or
ZONE)
Ambient Temperature Outdoor Air Node Name
Type: node
Required for Ambient Temperature Indicator=Outdoors
Uniform Skin Loss Coefficient per Unit Area to Ambient Temperature
Type: real number
Unit: W/m2-K
Minimum: 0.0
Skin Loss Fraction to Zone
Type: real number
Minimum: 0.0
Maximum: 1.0
Default: 1.0
Off Cycle Flue Loss Coefficient to Ambient Temperature
Type: real number
Unit: W/K
Minimum: 0.0
Off Cycle Flue Loss Fraction to Zone
Type: real number
Minimum: 0.0
Maximum: 1.0
Default: 1.0
Peak Use Flow Rate
Type: real number
Only used if Use Side Node connections are blank
Unit: m3/s
Minimum: 0.0
Use Flow Rate Fraction Schedule Name
Type: list of objects
(
SCHEDULE:COMPACT,
SCHEDULE:FILE,
SCHEDULE:YEAR,
SCHEDULE:CONSTANT,
EXTERNALINTERFACE:SCHEDULE or
EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE)
If blank, defaults to 1.0 at all times Only used if use side node connections are blank
Cold Water Supply Temperature Schedule Name
Type: list of objects
(
SCHEDULE:COMPACT,
SCHEDULE:FILE,
SCHEDULE:YEAR,
SCHEDULE:CONSTANT,
EXTERNALINTERFACE:SCHEDULE or
EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE)
Only used if use side node connections are blank Defaults to water temperatures calculated by Site:WaterMainsTemperature object
Use Side Inlet Node Name
Type: node
Use Side Outlet Node Name
Type: node
Use Side Effectiveness
Type: real number
The use side effectiveness in the stratified tank model is a simplified analogy of a heat exchanger's effectiveness. This effectiveness is equal to the fraction of use mass flow rate that directly mixes with the tank fluid. And one minus the effectiveness is the fraction that bypasses the tank. The use side mass flow rate that bypasses the tank is mixed with the fluid or water leaving the stratified tank.
Minimum: 0.0
Maximum: 1.0
Default: 1.0
Use Side Inlet Height
Type: real number
Defaults to bottom of tank
Unit: m
Minimum: 0.0
Default: 0.0
Use Side Outlet Height
Type: real number
Defaults to top of tank
Unit: m
Minimum: 0.0
Default: Autocalculate
Source Side Inlet Node Name
Type: node
Source Side Outlet Node Name
Type: node
Source Side Effectiveness
Type: real number
The source side effectiveness in the stratified tank model is a simplified analogy of a heat exchanger's effectiveness. This effectiveness is equal to the fraction of source mass flow rate that directly mixes with the tank fluid. And one minus the effectiveness is the fraction that bypasses the tank. The source side mass flow rate that bypasses the tank is mixed with the fluid or water leaving the stratified tank.
Maximum: 1.0
Default: 1.0
Source Side Inlet Height
Type: real number
Defaults to top of tank
Unit: m
Minimum: 0.0
Default: Autocalculate
Source Side Outlet Height
Type: real number
Defaults to bottom of tank
Unit: m
Minimum: 0.0
Default: 0.0
Inlet Mode
Type: choice
(Fixed or Seeking)
Default: Fixed
Use Side Design Flow Rate
Type: real number
Unit: m3/s
Minimum: 0.0
Default: autosize
Source Side Design Flow Rate
Type: real number
Unit: m3/s
Minimum: 0.0
Default: autosize
Indirect Water Heating Recovery Time
Type: real number
Parameter for autosizing design flow rates for indirectly heated water tanks time required to raise temperature of entire tank from 14.4C to 57.2C
Unit: hr
Default: 1.5
Number of Nodes
Type: integer
Minimum: 1
Maximum: 12
Default: 1
Additional Destratification Conductivity
Type: real number
Unit: W/m-K
Minimum: 0.0
Default: 0.0
Node 1 Additional Loss Coefficient
Type: real number
Unit: W/K
Default: 0.0
Node 2 Additional Loss Coefficient
Type: real number
Unit: W/K
Default: 0.0
Node 3 Additional Loss Coefficient
Type: real number
Unit: W/K
Default: 0.0
Node 4 Additional Loss Coefficient
Type: real number
Unit: W/K
Default: 0.0
Node 5 Additional Loss Coefficient
Type: real number
Unit: W/K
Default: 0.0
Node 6 Additional Loss Coefficient
Type: real number
Unit: W/K
Default: 0.0
Node 7 Additional Loss Coefficient
Type: real number
Unit: W/K
Default: 0.0
Node 8 Additional Loss Coefficient
Type: real number
Unit: W/K
Default: 0.0
Node 9 Additional Loss Coefficient
Type: real number
Unit: W/K
Default: 0.0
Node 10 Additional Loss Coefficient
Type: real number
Unit: W/K
Default: 0.0
Node 11 Additional Loss Coefficient
Type: real number
Unit: W/K
Default: 0.0
Node 12 Additional Loss Coefficient
Type: real number
Unit: W/K
Default: 0.0
Source Side Flow Control Mode
Type: choice
(StorageTank, IndirectHeatPrimarySetpoint or IndirectHeatAlternateSetpoint)
StorageTank mode always requests flow unless tank is at its Maximum Temperature Limit IndirectHeatPrimarySetpoint mode requests flow whenever primary setpoint for heater 1 calls for heat IndirectHeatAlternateSetpoint mode requests flow whenever alternate indirect setpoint calls for heat
Default: IndirectHeatPrimarySetpoint
Indirect Alternate Setpoint Temperature Schedule Name
Type: list of objects
(
SCHEDULE:COMPACT,
SCHEDULE:FILE,
SCHEDULE:YEAR,
SCHEDULE:CONSTANT,
EXTERNALINTERFACE:SCHEDULE or
EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE)
This field is only used if the previous is set to IndirectHeatAlternateSetpoint