STEAMEQUIPMENT

Sets internal gains for steam equipment in the zone.

Name
Type: alphanumeric

Zone or ZoneList Name
Type: list of objects (ZONE or ZONELIST)

Schedule Name
Type: list of objects (SCHEDULE:YEAR, SCHEDULE:FILE, SCHEDULE:COMPACT, EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE, EXTERNALINTERFACE:SCHEDULE or SCHEDULE:CONSTANT)
Units in Schedule should be fraction applied to design level of steam equipment, generally (0.0 - 1.0)

Design Level Calculation Method
Type: choice (EquipmentLevel, Watts/Area, Watts/Person, Power/Area or Power/Person)
The entered calculation method is used to create the maximum amount of steam equipment for this set of attributes Choices: EquipmentLevel => Design Level -- simply enter power input of equipment Watts/Area or Power/Area => Power per Zone Floor Area -- enter the number to apply. Value * Floor Area = Equipment Level Watts/Person or Power/Person => Power per Person -- enter the number to apply. Value * Occupants = Equipment Level
Default: EquipmentLevel

Design Level
Type: real number
Unit: W
Minimum: 0
Values in example files: 1050.0 W in all 1 example files

Power per Zone Floor Area
Type: real number
Unit: W/m2
Minimum: 0
Values in example files: empty in all 1 example files

Power per Person
Type: real number
Unit: W/person
Minimum: 0
Values in example files: empty in all 1 example files

Fraction Latent
Type: real number
Minimum: 0.0
Maximum: 1.0
Default: 0
Values in example files: 0.5 in all 1 example files

Fraction Radiant
Type: real number
Minimum: 0.0
Maximum: 1.0
Default: 0
Values in example files: 0.3 in all 1 example files

Fraction Lost
Type: real number
Minimum: 0.0
Maximum: 1.0
Default: 0
Values in example files: 0.0 in all 1 example files

End-Use Subcategory
Type: alphanumeric
Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
Default: General