REFRIGERATION:WALKIN
Works in conjunction with a compressor rack, a refrigeration system, or a refrigeration secondary system to simulate the performance of a walk-in cooler. The walk-in cooler model uses information at rated conditions along with input descriptions for heat transfer surfaces facing multiple zones to determine performance.
Name
Type: alphanumeric
Availability Schedule Name
Type: list of objects
(
SCHEDULE:FILE,
SCHEDULE:CONSTANT,
SCHEDULE:YEAR,
EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE,
SCHEDULE:COMPACT or
EXTERNALINTERFACE:SCHEDULE)
Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Rated Coil Cooling Capacity
Type: real number
Unit: W
Operating Temperature
Type: real number
Unit: C
Rated Cooling Source Temperature
Type: real number
If DXEvaporator, use evaporating temperature (saturated suction temperature) If BrineCoil, use Brine entering temperature used to set minimum suction pressure for DX systems and minimum brine temp for secondary systems
Unit: C
Minimum: -70.0
Maximum: 40.
Rated Total Heating Power
Type: real number
Include total for all anti-sweat, door, drip-pan, and floor heater power Do not include defrost heater power
Unit: W
Heating Power Schedule Name
Type: list of objects
(
SCHEDULE:FILE,
SCHEDULE:CONSTANT,
SCHEDULE:YEAR,
EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE,
SCHEDULE:COMPACT or
EXTERNALINTERFACE:SCHEDULE)
Values will be used to multiply the total heating power Values in the schedule should be between 0.0 and 1.0 For example, this could be used if display door antisweat heaters are turned off at night Defaults to always on if schedule name left blank.
Rated Cooling Coil Fan Power
Type: real number
Unit: W
Minimum: 0.
Default: 375.0
Rated Circulation Fan Power
Type: real number
Unit: W
Minimum: 0.0
Default: 0.0
Rated Total Lighting Power
Type: real number
Enter the total (display + task) installed lighting power.
Unit: W
Lighting Schedule Name
Type: list of objects
(
SCHEDULE:FILE,
SCHEDULE:CONSTANT,
SCHEDULE:YEAR,
EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE,
SCHEDULE:COMPACT or
EXTERNALINTERFACE:SCHEDULE)
The schedule should contain values between 0 and 1 Defaults to always on if schedule name left blank.
Defrost Type
Type: choice
(HotFluid, Electric, None or OffCycle)
HotFluid includes either hot gas defrost for a DX system or Hot Brine defrost if this walk in is cooled by brine from a secondary chiller
Default: Electric
Defrost Control Type
Type: choice
(TimeSchedule or TemperatureTermination)
Default: TimeSchedule
Defrost Schedule Name
Type: list of objects
(
SCHEDULE:FILE,
SCHEDULE:CONSTANT,
SCHEDULE:YEAR,
EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE,
SCHEDULE:COMPACT or
EXTERNALINTERFACE:SCHEDULE)
The schedule values should be 0 (off) or 1 (on)
Defrost Drip-Down Schedule Name
Type: list of objects
(
SCHEDULE:FILE,
SCHEDULE:CONSTANT,
SCHEDULE:YEAR,
EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE,
SCHEDULE:COMPACT or
EXTERNALINTERFACE:SCHEDULE)
The schedule values should be 0 (off) or 1 (on) The start time for each defrost period in this drip-down schedule should coincide with the start time for each defrost period in the defrost schedule (previous input field).The length of each defrost drip-down period must be greater than or equal to the corresponding defrost period specified in the defrost schedule. This extra time allows the melted frost to drip from the coil before refrigeration is restarted.
Defrost Power
Type: real number
Needed for all defrost types except none and offcycle
Unit: W
Minimum: 0.0
Temperature Termination Defrost Fraction to Ice
Type: real number
This is the portion of the defrost energy that is available to melt frost Needed only for defrost control type TemperatureTermination defaults to 0.7 for electric defrost and to 0.3 for hot fluid defrost
Unit: dimensionless
Maximum: 1.0
Restocking Schedule Name
Type: list of objects
(
SCHEDULE:FILE,
SCHEDULE:CONSTANT,
SCHEDULE:YEAR,
EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE,
SCHEDULE:COMPACT or
EXTERNALINTERFACE:SCHEDULE)
Schedule values should be in units of Watts Leave this field blank if no restocking is to be modeled
Average Refrigerant Charge Inventory
Type: real number
This value is only used if the Cooling Source Type is DXEvaporator
Unit: kg
Default: 0.0
Insulated Floor Surface Area
Type: real number
Floor area of walk-in cooler
Unit: m2
Insulated Floor U-Value
Type: real number
The default value corresponds to R18 [ft2-F-hr/Btu] To convert other IP R-values to U, divide 5.678 by the R-value Some examples: R15 is U 0.3785 W/m2-K R5 is U 1.136 W/m2-K
Unit: W/m2-K
Default: 0.3154
Zone 1 Name
Type: list of objects
( or
ZONE)
This must be a controlled zone and appear in a ZoneHVAC:EquipmentConnections object. The walk-in cooler can face multiple zones. The heat exchange with each zone must be input separately
Total Insulated Surface Area Facing Zone 1
Type: real number
Area should include walls and ceilings, but not doors
Unit: m2
Insulated Surface U-Value Facing Zone 1
Type: real number
The default value corresponds to R18 [ft2-F-hr/Btu] To convert other IP R-values to U, divide 5.678 by the R-value Some examples: R15 is U 0.3785 W/m2-K R5 is U 1.136 W/m2-K
Unit: W/m2-K
Default: 0.3154
Area of Glass Reach In Doors Facing Zone 1
Type: real number
Unit: m2
Default: 0.0
Height of Glass Reach In Doors Facing Zone 1
Type: real number
Unit: m
Default: 1.5
Glass Reach In Door U Value Facing Zone 1
Type: real number
The default value corresponds to R5 [ft2-F-hr/Btu] To convert other IP R-values to U, divide 5.678 by the R-value
Unit: W/m2-K
Default: 1.136
Glass Reach In Door Opening Schedule Name Facing Zone 1
Type: list of objects
(
SCHEDULE:FILE,
SCHEDULE:CONSTANT,
SCHEDULE:YEAR,
EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE,
SCHEDULE:COMPACT or
EXTERNALINTERFACE:SCHEDULE)
Schedule values should all be between 0.0 and 1.0. For example, if the door is open 30% of the time during working hours, then the schedule would hold the value 0.3 during working hours and 0 during other hours If no schedule name is entered, default is 5% open time during all hours
Area of Stocking Doors Facing Zone 1
Type: real number
Unit: m2
Default: 0.0
Height of Stocking Doors Facing Zone 1
Type: real number
Unit: m
Default: 3.0
Stocking Door U Value Facing Zone 1
Type: real number
The default value corresponds to R15 [ft2-F-hr/Btu] To convert other IP R-values to U, divide 5.678 by the R-value Some examples: R5 is U 1.136 W/m2-K R18 is U 0.3154 W/m2-K
Unit: W/m2-K
Default: 0.3785
Stocking Door Opening Schedule Name Facing Zone 1
Type: list of objects
(
SCHEDULE:FILE,
SCHEDULE:CONSTANT,
SCHEDULE:YEAR,
EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE,
SCHEDULE:COMPACT or
EXTERNALINTERFACE:SCHEDULE)
Schedule values should all be between 0.0 and 1.0. For example, if the door is open 30% of the time during working hours, then the schedule would hold the value 0.3 during working hours and 0 during other hours If no schedule name is entered, default is 5% open time during all hours
Stocking Door Opening Protection Type Facing Zone 1
Type: choice
(None, AirCurtain or StripCurtain)
Use StripCurtain for hanging strips or airlock vestibules
Default: AirCurtain
Zone 2 Name
Type: list of objects
( or
ZONE)
Required if more than one zone This must be a controlled zone and appear in a ZoneHVAC:EquipmentConnections object.
Total Insulated Surface Area Facing Zone 2
Type: real number
Area should include walls and ceilings, but not doors required if more than one zone
Unit: m2
Insulated Surface U-Value Facing Zone 2
Type: real number
The default value corresponds to R18 [ft2-F-hr/Btu] To convert other IP R-values to U, divide 5.678 by the R-value Some examples: R15 is U 0.3785 W/m2-K R5 is U 1.136 W/m2-K
Unit: W/m2-K
Default: 0.3154
Area of Glass Reach In Doors Facing Zone 2
Type: real number
Unit: m2
Default: 0.0
Height of Glass Reach In Doors Facing Zone 2
Type: real number
Unit: m
Default: 1.5
Glass Reach In Door U Value Facing Zone 2
Type: real number
The default value corresponds to R5 [ft2-F-hr/Btu] To convert other IP R-values to U, divide 5.678 by the R-value
Unit: W/m2-K
Default: 1.136
Glass Reach In Door Opening Schedule Name Facing Zone 2
Type: list of objects
(
SCHEDULE:FILE,
SCHEDULE:CONSTANT,
SCHEDULE:YEAR,
EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE,
SCHEDULE:COMPACT or
EXTERNALINTERFACE:SCHEDULE)
Schedule values should all be between 0.0 and 1.0. For example, if the door is open 30% of the time during working hours, then the schedule would hold the value 0.3 during working hours and 0 during other hours If no schedule name is entered, default is 5% open time during all hours
Area of Stocking Doors Facing Zone 2
Type: real number
Unit: m2
Default: 0.0
Height of Stocking Doors Facing Zone 2
Type: real number
Unit: m
Default: 3.0
Stocking Door U Value Facing Zone 2
Type: real number
The default value corresponds to R15 [ft2-F-hr/Btu] To convert other IP R-values to U, divide 5.678 by the R-value Some examples: R5 is U 1.136 W/m2-K R18 is U 0.3154 W/m2-K
Unit: W/m2-K
Default: 0.3785
Stocking Door Opening Schedule Name Facing Zone 2
Type: list of objects
(
SCHEDULE:FILE,
SCHEDULE:CONSTANT,
SCHEDULE:YEAR,
EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE,
SCHEDULE:COMPACT or
EXTERNALINTERFACE:SCHEDULE)
Schedule values should all be between 0.0 and 1.0. For example, if the door is open 30% of the time during working hours, then the schedule would hold the value 0.3 during working hours and 0 during other hours If no schedule name is entered, default is 5% open time during all hours
Stocking Door Opening Protection Type Facing Zone 2
Type: choice
(None, AirCurtain or StripCurtain)
Use StripCurtain for hanging strips or airlock vestibules last extensible set begins here dup remaining 12 lines as many times as there are zones exchanging heat with walk-in Move the ending semicolon and increment the field numbers.
Default: AirCurtain
Zone 3 Name
Type: list of objects
( or
ZONE)
This must be a controlled zone and appear in a ZoneHVAC:EquipmentConnections object. required if more than two zones
Total Insulated Surface Area Facing Zone 3
Type: real number
Required if more than two zones Area should include walls and ceilings, but not doors
Unit: m2
Insulated Surface U-Value Facing Zone 3
Type: real number
The default value corresponds to R18 [ft2-F-hr/Btu] To convert other IP R-values to U, divide 5.678 by the R-value Some examples: R15 is U 0.3785 W/m2-K R5 is U 1.136 W/m2-K
Unit: W/m2-K
Default: 0.3154
Area of Glass Reach In Doors Facing Zone 3
Type: real number
Unit: m2
Default: 0.0
Height of Glass Reach In Doors Facing Zone 3
Type: real number
Unit: m
Default: 1.5
Glass Reach In Door U Value Facing Zone 3
Type: real number
The default value corresponds to R5 [ft2-F-hr/Btu] To convert other IP R-values to U, divide 5.678 by the R-value
Unit: W/m2-K
Default: 1.136
Glass Reach In Door Opening Schedule Name Facing Zone 3
Type: list of objects
(
SCHEDULE:FILE,
SCHEDULE:CONSTANT,
SCHEDULE:YEAR,
EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE,
SCHEDULE:COMPACT or
EXTERNALINTERFACE:SCHEDULE)
Schedule values should all be between 0.0 and 1.0. For example, if the door is open 30% of the time during working hours, then the schedule would hold the value 0.3 during working hours and 0 during other hours If no schedule name is entered, default is 5% open time during all hours
Area of Stocking Doors Facing Zone 3
Type: real number
Unit: m2
Default: 0.0
Height of Stocking Doors Facing Zone 3
Type: real number
Unit: m
Default: 3.0
Stocking Door U Value Facing Zone 3
Type: real number
The default value corresponds to R15 [ft2-F-hr/Btu] To convert other IP R-values to U, divide 5.678 by the R-value Some examples: R5 is U 1.136 W/m2-K R18 is U 0.3154 W/m2-K
Unit: W/m2-K
Default: 0.3785
Stocking Door Opening Schedule Name Facing Zone 3
Type: list of objects
(
SCHEDULE:FILE,
SCHEDULE:CONSTANT,
SCHEDULE:YEAR,
EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE,
SCHEDULE:COMPACT or
EXTERNALINTERFACE:SCHEDULE)
Schedule values should all be between 0.0 and 1.0. For example, if the door is open 30% of the time during working hours, then the schedule would hold the value 0.3 during working hours and 0 during other hours If no schedule name is entered, default is 5% open time during all hours
Stocking Door Opening Protection Type Facing Zone 3
Type: choice
(None, AirCurtain or StripCurtain)
Use StripCurtain for hanging strips or airlock vestibules
Default: AirCurtain