REFRIGERATION:SYSTEM
Simulates the performance of a supermarket refrigeration system when used along with other objects to define the refrigeration load(s), the compressor(s), and the condenser.
Name
Type: alphanumeric
Refrigerated Case or Walkin or CaseAndWalkInList Name
Type: list of objects
(
REFRIGERATION:CASE,
REFRIGERATION:AIRCHILLER,
REFRIGERATION:WALKIN or
REFRIGERATION:CASEANDWALKINLIST)
Enter the name of a Refrigeration:Case or Refrigeration:WalkIn object. If there is more than one refrigerated case or walk-in served by this system, enter the name of a Refrigeration:CaseAndWalkInList object. Only cases and walkins served directly by the system should be included in this list. Any cases served indirectly via a secondary chiller should NOT be included in this list
Refrigeration Transfer Load or TransferLoad List Name
Type: list of objects
(
REFRIGERATION:SECONDARYSYSTEM,
REFRIGERATION:CONDENSER:CASCADE or
REFRIGERATION:TRANSFERLOADLIST)
Enter the name of a Refrigeration:SecondarySystem object OR a Refrigeration:Condenser:Cascade object OR, a Refrigeration:TransferLoadList object. A transfer load is identified as one which moves the load from one system to another. So if you have more than one such load (including cascade condensers and secondary loops) served by the same system, use a TransferLoadList object.
Refrigeration Condenser Name
Type: list of objects
(
REFRIGERATION:CONDENSER:EVAPORATIVECOOLED,
REFRIGERATION:CONDENSER:AIRCOOLED,
REFRIGERATION:CONDENSER:CASCADE or
REFRIGERATION:CONDENSER:WATERCOOLED)
Compressor or CompressorList Name
Type: list of objects
(
REFRIGERATION:COMPRESSOR or
REFRIGERATION:COMPRESSORLIST)
Minimum Condensing Temperature
Type: real number
Related to the proper operation of the thermal expansion valves and compressors
Unit: C
Refrigeration System Working Fluid Type
Type: list of objects
Fluid property data for the refrigerant must be entered. The fluid property data, including the objects: FluidProperties:Name, FluidProperties:Temperatures, FluidProperties:Saturated and FluidProperties:Superheated can be copied from the FluidPropertiesRefData.idf dataset
Suction Temperature Control Type
Type: choice
(FloatSuctionTemperature or ConstantSuctionTemperature)
Default: ConstantSuctionTemperature
Mechanical Subcooler Name
Type: list of objects
( or
REFRIGERATION:SUBCOOLER)
Optional Field Recipient of refrigeration capacity, that is receives cool liquid from another refrigeration system to help meet aggregate case loads
Liquid Suction Heat Exchanger Subcooler Name
Type: list of objects
( or
REFRIGERATION:SUBCOOLER)
Optional Field Liquid Suction Heat Exchanger Name, or leave blank
Sum UA Suction Piping
Type: real number
Use only if you want to include suction piping heat gain in refrigeration load
Unit: W/K
Default: 0.0
Suction Piping Zone Name
Type: list of objects
( or
ZONE)
This will be used to determine the temperature used for distribution piping heat gain and the pipe heat gains as cooling credit for the zone. Required only if Sum UA Distribution Piping >0.0
End-Use Subcategory
Type: alphanumeric
Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
Default: General
Number of Compressor Stages
Type: choice
(1 or 2)
Default: 1
Intercooler Type
Type: choice
(None, Flash Intercooler or Shell-and-Coil Intercooler)
Default: None
Shell-and-Coil Intercooler Effectiveness
Type: real number
Default: 0.8
High-Stage Compressor or CompressorList Name
Type: list of objects
(
REFRIGERATION:COMPRESSOR or
REFRIGERATION:COMPRESSORLIST)