PIPINGSYSTEM:UNDERGROUND:DOMAIN
The ground domain object for underground piping system simulation.
Name
Type: alphanumeric
Xmax
Type: real number
Domain extent in the local 'X' direction
Unit: m
Ymax
Type: real number
Domain extent in the local 'Y' direction
Unit: m
Zmax
Type: real number
Domain extent in the local 'Y' direction
Unit: m
X-Direction Mesh Density Parameter
Type: integer
If mesh type is symmetric geometric, this should be an even number.
Default: 4
X-Direction Mesh Type
Type: choice
(Uniform or SymmetricGeometric)
X-Direction Geometric Coefficient
Type: real number
Optional Only used if mesh type is symmetric geometric
Minimum: 1
Maximum: 2
Default: 1.3
Y-Direction Mesh Density Parameter
Type: integer
If mesh type is symmetric geometric, this should be an even number.
Default: 4
Y-Direction Mesh Type
Type: choice
(Uniform or SymmetricGeometric)
Y-Direction Geometric Coefficient
Type: real number
Optional Only used if mesh type is symmetric geometric
Minimum: 1
Maximum: 2
Default: 1.3
Z-Direction Mesh Density Parameter
Type: integer
If mesh type is symmetric geometric, this should be an even number.
Default: 4
Z-Direction Mesh Type
Type: choice
(Uniform or SymmetricGeometric)
Z-Direction Geometric Coefficient
Type: real number
Optional Only used if mesh type is symmetric geometric
Minimum: 1
Maximum: 2
Default: 1.3
Soil Thermal Conductivity
Type: real number
Unit: W/m-K
Soil Density
Type: real number
Unit: kg/m3
Soil Specific Heat
Type: real number
This is a dry soil property, which is adjusted for freezing effects by the simulation algorithm.
Unit: J/kg-K
Soil Moisture Content Volume Fraction
Type: real number
Unit: percent
Minimum: 0
Maximum: 100
Default: 30
Soil Moisture Content Volume Fraction at Saturation
Type: real number
Unit: percent
Minimum: 0
Maximum: 100
Default: 50
Undisturbed Ground Temperature Model Type
Type: choice
(Site:GroundTemperature:Undisturbed:FiniteDifference, Site:GroundTemperature:Undisturbed:KusudaAchenbach or Site:GroundTemperature:Undisturbed:Xing)
Undisturbed Ground Temperature Model Name
Type: list of objects
(
SITE:GROUNDTEMPERATURE:UNDISTURBED:XING,
SITE:GROUNDTEMPERATURE:UNDISTURBED:KUSUDAACHENBACH or
SITE:GROUNDTEMPERATURE:UNDISTURBED:FINITEDIFFERENCE)
This Domain Includes Basement Surface Interaction
Type: choice
(Yes or No)
If Yes, then the following basement inputs are used if No, then the following basement inputs are *ignored*
Default: No
Width of Basement Floor in Ground Domain
Type: real number
Required only if Domain Has Basement Interaction
Unit: m
Depth of Basement Wall In Ground Domain
Type: real number
Required only if Domain Has Basement Interaction
Unit: m
Shift Pipe X Coordinates By Basement Width
Type: choice
(Yes or No)
Required only if Domain Has Basement Interaction
Name of Basement Wall Boundary Condition Model
Type: list of objects
( or
SURFACEPROPERTY:OTHERSIDECONDITIONSMODEL)
Required only if Domain Has Basement Interaction
Name of Basement Floor Boundary Condition Model
Type: list of objects
( or
SURFACEPROPERTY:OTHERSIDECONDITIONSMODEL)
Required only if Domain Has Basement Interaction
Convergence Criterion for the Outer Cartesian Domain Iteration Loop
Type: real number
Unit: deltaC
Minimum: 0.000001
Maximum: 0.5
Default: 0.001
Maximum Iterations in the Outer Cartesian Domain Iteration Loop
Type: integer
Minimum: 3
Maximum: 10000
Default: 500
Evapotranspiration Ground Cover Parameter
Type: real number
This specifies the ground cover effects during evapotranspiration calculations. The value roughly represents the following cases: = 0 : concrete or other solid, non-permeable ground surface material = 0.5 : short grass, much like a manicured lawn = 1 : standard reference state (12 cm grass) = 1.5 : wild growth
Minimum: 0
Maximum: 1.5
Default: 0.4
Number of Pipe Circuits Entered for this Domain
Type: integer
Minimum: 1
Pipe Circuit 1
Type: list of objects
( or
PIPINGSYSTEM:UNDERGROUND:PIPECIRCUIT)
Name of a pipe circuit to be simulated in this domain
Pipe Circuit 2
Type: list of objects
( or
PIPINGSYSTEM:UNDERGROUND:PIPECIRCUIT)
Optional Name of a pipe circuit to be simulated in this domain
Pipe Circuit 3
Type: list of objects
( or
PIPINGSYSTEM:UNDERGROUND:PIPECIRCUIT)
Optional Name of a pipe circuit to be simulated in this domain
Pipe Circuit 4
Type: list of objects
( or
PIPINGSYSTEM:UNDERGROUND:PIPECIRCUIT)
Optional Name of a pipe circuit to be simulated in this domain
Pipe Circuit 5
Type: list of objects
( or
PIPINGSYSTEM:UNDERGROUND:PIPECIRCUIT)
Optional Name of a pipe circuit to be simulated in this domain
Pipe Circuit 6
Type: list of objects
( or
PIPINGSYSTEM:UNDERGROUND:PIPECIRCUIT)
Optional Name of a pipe circuit to be simulated in this domain