HVACTEMPLATE:SYSTEM:UNITARYSYSTEM
Unitary HVAC system with optional cooling and heating. Supports DX and chilled water, cooling, gas, electric, and hot water heating, air-to-air and water-to-air heat pumps.
Name
System Availability Schedule Name
Type: list of objects
(
SCHEDULE:YEAR,
SCHEDULE:FILE,
SCHEDULE:COMPACT,
EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE,
EXTERNALINTERFACE:SCHEDULE or
SCHEDULE:CONSTANT)
If blank, always available. Also see Supply Fan Operating Mode Schedule Name field.
Control Type
Type: choice
(Load or SetPoint)
Load control requires a Controlling Zone name. SetPoint control requires set points at coil outlet nodes. The user must add appropriate SetpointManager objects to the idf file.
Default: Load
Control Zone or Thermostat Location Name
Type: list of objects
( or
ZONE)
This field is required if Control Type is Load.
Cooling Supply Air Flow Rate
Type: real number
Supply air flow rate during cooling operation This field may be set to "autosize". If a value is entered, it will *not* be multiplied by any sizing factor or by zone multipliers. If using zone multipliers a value entered here must be large enough to serve the multiplied zones.
Unit: m3/s
Default: autosize
Heating Supply Air Flow Rate
Type: real number
Supply air flow rate during heating operation This field may be set to "autosize". If a value is entered, it will *not* be multiplied by any sizing factor or by zone multipliers. If using zone multipliers a value entered here must be large enough to serve the multiplied zones.
Unit: m3/s
Default: autosize
No Load Supply Air Flow Rate
Type: real number
Supply air flow rate when no cooling or heating is needed Only used when heat pump fan operating mode is Continuous. This air flow rate is used when no heating or cooling is required and the DX coil compressor is off. If this field is left blank or zero, the supply air flow rate from the previous on cycle (either cooling or heating) is used. This field may be set to "autosize". If a value is entered, it will *not* be multiplied by any sizing factor or by zone multipliers. If using zone multipliers a value entered here must be large enough to serve the multiplied zones.
Unit: m3/s
Minimum: 0
Default: autosize
Supply Fan Operating Mode Schedule Name
Type: list of objects
(
SCHEDULE:YEAR,
SCHEDULE:FILE,
SCHEDULE:COMPACT,
EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE,
EXTERNALINTERFACE:SCHEDULE or
SCHEDULE:CONSTANT)
Refers to a schedule to specify unitary supply fan operating mode. Schedule values of 0 indicate cycling fan (auto) Schedule values of 1 indicate continuous fan (on) If this field is left blank, a schedule of always zero (cycling fan) will be used.
Supply Fan Placement
Type: choice
(BlowThrough or DrawThrough)
Default: BlowThrough
Supply Fan Total Efficiency
Maximum: 1.0
Default: 0.7
Supply Fan Delta Pressure
Unit: Pa
Minimum: 0
Default: 600
Supply Fan Motor Efficiency
Maximum: 1.0
Default: 0.9
Supply Fan Motor in Air Stream Fraction
Minimum: 0.0
Maximum: 1.0
Default: 1.0
Cooling Coil Type
Type: choice
(SingleSpeedDX, TwoSpeedDX, MultiSpeedDX, TwoStageDX, TwoStageHumidityControlDX, HeatExchangerAssistedDX, SingleSpeedDXWaterCooled, ChilledWater, ChilledWaterDetailedFlatModel, HeatExchangerAssistedChilledWater or None)
Default: SingleSpeedDX
Number of Speeds for Cooling
Type: integer
Used only for Cooling Coil Type = MultiSpeedDX.
Minimum: 0
Maximum: 4
Default: 1
Cooling Coil Availability Schedule Name
Type: list of objects
(
SCHEDULE:YEAR,
SCHEDULE:FILE,
SCHEDULE:COMPACT,
EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE,
EXTERNALINTERFACE:SCHEDULE or
SCHEDULE:CONSTANT)
If blank, always on
Cooling Design Supply Air Temperature
Used for sizing.
Unit: C
Default: 12.8
DX Cooling Coil Gross Rated Total Capacity
Total cooling capacity not accounting for the effect of supply air fan heat Rating point: air entering the cooling coil at 26.7 C dry-bulb/19.4 C wet-bulb, and air entering the outdoor condenser coil at 35 C dry-bulb/23.9 C wet-bulb
Unit: W
Default: autosize
DX Cooling Coil Gross Rated Sensible Heat Ratio
Rated sensible heat ratio (gross sensible capacity/gross total capacity) Sensible and total capacities do not include effect of supply fan heat
Minimum: 0.5
Maximum: 1.0
Default: autosize
DX Cooling Coil Gross Rated COP
Gross cooling capacity divided by power input to the compressor and outdoor fan, does not include supply fan heat or supply fan electric power input
Unit: W/W
Default: 3.0
Heating Coil Type
Type: choice
(Electric, Gas, HotWater, SingleSpeedDXHeatPumpAirSource, MultiSpeedDXHeatPumpAirSource, SingleSpeedDXHeatPumpWaterSource, MultiStageElectric, MultiStageGas or None)
Default: Gas
Number of Speeds or Stages for Heating
Type: integer
Used only for Heating Coil Type = MultiSpeedDXHeatPumpAirSource), MultiStageElectric, or MultiStageGas.
Minimum: 0
Maximum: 4
Default: 1
Heating Coil Availability Schedule Name
Type: list of objects
(
SCHEDULE:YEAR,
SCHEDULE:FILE,
SCHEDULE:COMPACT,
EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE,
EXTERNALINTERFACE:SCHEDULE or
SCHEDULE:CONSTANT)
If blank, always on
Heating Design Supply Air Temperature
Used for sizing.
Unit: C
Default: 50.0
Heating Coil Gross Rated Capacity
Type: real number
Rated heating capacity excluding the effect of supply air fan heat Rating point outdoor dry-bulb temp 8.33 C, outdoor wet-bulb temp 6.11 C Rating point heating coil entering air dry-bulb 21.11 C, coil entering wet-bulb 15.55 C
Unit: W
Default: autosize
Gas Heating Coil Efficiency
Minimum: 0.0
Maximum: 1.0
Default: 0.8
Gas Heating Coil Parasitic Electric Load
Unit: W
Minimum: 0.0
Default: 0.0
Heat Pump Heating Coil Gross Rated COP
Heating Coil Rated Capacity divided by power input to the compressor and outdoor fan, does not include supply air fan heat or supply air fan electrical energy. Rating point outdoor dry-bulb temp 8.33 C, outdoor wet-bulb temp 6.11 C Rating point heating coil entering air dry-bulb 21.11 C, coil entering wet-bulb 15.55 C Applies only to DX coils
Unit: W/W
Default: 2.75
Heat Pump Heating Minimum Outdoor Dry-Bulb Temperature
Type: real number
Unit: C
Minimum: -20.0
Default: -8.0
Heat Pump Defrost Maximum Outdoor Dry-Bulb Temperature
Type: real number
Unit: C
Minimum: 0.0
Maximum: 7.22
Default: 5.0
Heat Pump Defrost Strategy
Type: choice
(ReverseCycle or Resistive)
Default: ReverseCycle
Heat Pump Defrost Control
Type: choice
(Timed or OnDemand)
Default: Timed
Heat Pump Defrost Time Period Fraction
Type: real number
Fraction of time in defrost mode only applicable if Timed defrost control is specified
Minimum: 0.0
Default: 0.058333
Supplemental Heating or Reheat Coil Type
Type: choice
(Electric, Gas, HotWater, DesuperHeater or None)
Default: None
Supplemental Heating or Reheat Coil Availability Schedule Name
Type: list of objects
(
SCHEDULE:YEAR,
SCHEDULE:FILE,
SCHEDULE:COMPACT,
EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE,
EXTERNALINTERFACE:SCHEDULE or
SCHEDULE:CONSTANT)
If blank, always on
Supplemental Heating or Reheat Coil Capacity
Unit: W
Default: autosize
Supplemental Heating or Reheat Coil Maximum Outdoor Dry-Bulb Temperature
Type: real number
Supplemental heater will not operate when outdoor temperature exceeds this value.
Unit: C
Maximum: 21.0
Default: 21.0
Supplemental Gas Heating or Reheat Coil Efficiency
Applies only if Supplemental Heating Coil Type is Gas
Minimum: 0.0
Maximum: 1.0
Default: 0.8
Supplemental Gas Heating or Reheat Coil Parasitic Electric Load
Applies only if Supplemental Heating Coil Type is Gas
Unit: W
Minimum: 0.0
Default: 0.0
Maximum Outdoor Air Flow Rate
Unit: m3/s
Minimum: 0.0
Default: autosize
Minimum Outdoor Air Flow Rate
Unit: m3/s
Minimum: 0.0
Default: autosize
Minimum Outdoor Air Schedule Name
Type: list of objects
(
SCHEDULE:YEAR,
SCHEDULE:FILE,
SCHEDULE:COMPACT,
EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE,
EXTERNALINTERFACE:SCHEDULE or
SCHEDULE:CONSTANT)
Schedule values multiply the minimum outdoor air flow rate If blank, multiplier is always one
Economizer Type
Type: choice
(FixedDryBulb, FixedEnthalpy, DifferentialDryBulb, DifferentialEnthalpy, FixedDewPointAndDryBulb, ElectronicEnthalpy, DifferentialDryBulbAndEnthalpy or NoEconomizer)
Default: NoEconomizer
Economizer Lockout
Type: choice
(NoLockout, LockoutWithHeating or LockoutWithCompressor)
Default: NoLockout
Economizer Maximum Limit Dry-Bulb Temperature
Type: real number
Enter the maximum outdoor dry-bulb temperature limit for FixedDryBulb economizer control type. No input or blank input means this limit is not operative. Limit is applied regardless of economizer control type.
Unit: C
Economizer Maximum Limit Enthalpy
Type: real number
Enter the maximum outdoor enthalpy limit for FixedEnthalpy economizer control type. No input or blank input means this limit is not operative Limit is applied regardless of economizer control type.
Unit: J/kg
Economizer Maximum Limit Dewpoint Temperature
Type: real number
Enter the maximum outdoor dewpoint temperature limit for FixedDewPointAndDryBulb economizer control type. No input or blank input means this limit is not operative. Limit is applied regardless of economizer control type.
Unit: C
Economizer Minimum Limit Dry-Bulb Temperature
Type: real number
Enter the minimum outdoor dry-bulb temperature limit for economizer control. No input or blank input means this limit is not operative Limit is applied regardless of economizer control type.
Unit: C
Supply Plenum Name
Type: list of objects
( or
ZONE)
Plenum zone name. Supply plenum serves all zones on this system. Blank if none.
Return Plenum Name
Type: list of objects
( or
ZONE)
Plenum zone name. Return plenum serves all zones on this system. Blank if none.
Heat Recovery Type
Type: choice
(None, Sensible or Enthalpy)
Default: None
Sensible Heat Recovery Effectiveness
Minimum: 0.0
Maximum: 1.0
Default: 0.70
Latent Heat Recovery Effectiveness
Applicable only if Heat Recovery Type is Enthalpy.
Minimum: 0.0
Maximum: 1.0
Default: 0.65
Heat Recovery Heat Exchanger Type
Type: choice
(Plate or Rotary)
Default: Plate
Heat Recovery Frost Control Type
Type: choice
(None, ExhaustAirRecirculation, ExhaustOnly or MinimumExhaustTemperature)
Default: None
Dehumidification Control Type
Type: choice
(None, CoolReheat or Multimode)
None = meet sensible load only CoolReheat = cool beyond the dry-bulb setpoint, reheat with reheat coil If no reheat coil specified, cold supply temps may occur. Multimode = activate enhanced dehumidification mode as needed and meet sensible load. Valid only for Cooling Coil Type = TwoStageHumidityControlDX or HeatExchangerAssistedDX
Default: None
Dehumidification Relative Humidity Setpoint
Type: real number
Zone relative humidity setpoint in percent (0 to 100) Ignored if Dehumidification Relative Humidity Setpoint Schedule specified below
Unit: percent
Minimum: 0.0
Maximum: 100.0
Default: 60.0
Dehumidification Relative Humidity Setpoint Schedule Name
Type: list of objects
(
SCHEDULE:YEAR,
SCHEDULE:FILE,
SCHEDULE:COMPACT,
EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE,
EXTERNALINTERFACE:SCHEDULE or
SCHEDULE:CONSTANT)
Leave blank to use constant setpoint specified in Dehumidification Relative Humidity Setpoint above. Schedule values must be in percent relative humidity (0 to 100).
Humidifier Type
Type: choice
(None or ElectricSteam)
Default: None
Humidifier Availability Schedule Name
Type: list of objects
(
SCHEDULE:YEAR,
SCHEDULE:FILE,
SCHEDULE:COMPACT,
EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE,
EXTERNALINTERFACE:SCHEDULE or
SCHEDULE:CONSTANT)
If blank, always available
Humidifier Rated Capacity
Type: real number
Moisture output rate at full rated power input. The humidifier does not currently autosize, so the default is very large to allow for adequate capacity.
Unit: m3/s
Minimum: 0.0
Default: 0.000001
Humidifier Rated Electric Power
Type: real number
Electric power input at rated capacity moisture output. Power consumption is proportional to moisture output with no part-load penalty.
Unit: W
Minimum: 0.0
Default: autosize
Humidifier Control Zone Name
Type: list of objects
( or
ZONE)
Zone name where humidistat is located
Humidifier Relative Humidity Setpoint
Type: real number
Zone relative humidity setpoint in percent (0 to 100). Ignored if Humidifier Relative Humidity Setpoint Schedule specified below
Unit: percent
Minimum: 0.0
Maximum: 100.0
Default: 30.0
Humidifier Relative Humidity Setpoint Schedule Name
Type: list of objects
(
SCHEDULE:YEAR,
SCHEDULE:FILE,
SCHEDULE:COMPACT,
EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE,
EXTERNALINTERFACE:SCHEDULE or
SCHEDULE:CONSTANT)
Leave blank to use constant setpoint specified in Humidifier Relative Humidity Setpoint above.Schedule values must be in percent relative humidity (0 to 100).
Sizing Option
Type: choice
(Coincident or NonCoincident)
Select whether autosized system supply flow rate is the sum of Coincident or NonCoincident zone air flow rates.
Default: NonCoincident
Return Fan
Type: choice
(Yes or No)
Specifies if the system has a return fan.
Default: No
Return Fan Total Efficiency
Maximum: 1.0
Default: 0.7
Return Fan Delta Pressure
Unit: Pa
Minimum: 0
Default: 300
Return Fan Motor Efficiency
Maximum: 1.0
Default: 0.9
Return Fan Motor in Air Stream Fraction
Minimum: 0.0
Maximum: 1.0
Default: 1.0