HVACTEMPLATE:PLANT:TOWER
This object adds a cooling tower to an HVACTemplate:Plant:ChilledWaterLoop or MixedWaterLoop.
Name
Tower Type
Type: choice
(SingleSpeed or TwoSpeed)
High Speed Nominal Capacity
Applicable for tower type SingleSpeed and TwoSpeed Nominal tower capacity with entering water at 35C (95F), leaving water at 29.44C (85F), entering air at 25.56C (78F) wet-bulb temperature and 35C (95F) dry-bulb temperature, with the tower fan operating at high speed. Design water flow rate assumed to be 5.382E-8 m3/s per watt(3 gpm/ton). Nominal tower capacity times (1.25) gives the actual tower heat rejection at these operating conditions.
Unit: W
Default: autosize
High Speed Fan Power
Applicable for tower type SingleSpeed and TwoSpeed
Unit: W
Default: autosize
Low Speed Nominal Capacity
Applicable only for Tower Type TwoSpeed Nominal tower capacity with entering water at 35C (95F), leaving water at 29.44C (85F), entering air at 25.56C (78F) wet-bulb temperature and 35C (95F) dry-bulb temperature, with the tower fan operating at low speed. Design water flow rate assumed to be 5.382E-8 m3/s per watt of tower high-speed nominal capacity (3 gpm/ton). Nominal tower capacity times (1.25) gives the actual tower heat rejection at these operating conditions.
Unit: W
Default: autosize
Low Speed Fan Power
Applicable only for Tower Type TwoSpeed
Unit: W
Default: autosize
Free Convection Capacity
Applicable for Tower Type SingleSpeed and TwoSpeed Tower capacity in free convection regime with entering water at 35C (95F), leaving water at 29.44C (85F), entering air at 25.56C (78F) wet-bulb temperature and 35C (95F) dry-bulb temperature. Design water flow rate assumed to be 5.382E-8 m3/s per watt of tower high-speed nominal capacity (3 gpm/ton). Tower free convection capacity times (1.25) gives the actual tower heat rejection at these operating conditions.
Unit: W
Minimum: 0.0
Default: autosize
Priority
Applicable for all Tower Types If Condenser Plant Operation Scheme Type=Default in HVACTemplate:Plant:ChilledWaterLoop, then equipment operates in Priority order, 1, 2, 3, etc.
Sizing Factor
Type: real number
Multiplies the autosized capacity and flow rates
Default: 1.0
Template Plant Loop Type
Type: choice
(ChilledWater or MixedWater)
Specifies if this tower serves a template chilled water loop or mixed water loop If left blank, will serve a chilled water loop if present, or a mixed water loop (if no chilled water loop is present).