GROUNDHEATEXCHANGER:SLINKY
This models a slinky horizontal heat exchanger placed in a series of trenches The model uses the model developed by: Xiong, Z., D.E. Fisher, and J.D. Spitler. 2015. Development and Validation of a Slinky Ground Heat Exchanger Model. Applied Energy 141: 57-69.
Name
Inlet Node Name
Type: node
Outlet Node Name
Type: node
Design Flow Rate
Type: real number
Unit: m3/s
Default: 0.002
Soil Thermal Conductivity
Type: real number
Unit: W/m-K
Default: 1.08
Soil Density
Type: real number
Unit: kg/m3
Default: 962
Soil Specific Heat
Type: real number
Unit: J/kg-K
Default: 2576
Pipe Thermal Conductivity
Type: real number
Unit: W/m-K
Default: 0.4
Pipe Density
Type: real number
Unit: kg/m3
Default: 641
Pipe Specific Heat
Type: real number
Unit: J/kg-K
Default: 2405
Pipe Outer Diameter
Type: real number
Unit: m
Default: 0.02667
Pipe Thickness
Type: real number
Unit: m
Default: 0.002413
Heat Exchanger Configuration
Type: choice
(Vertical or Horizontal)
This is the orientation of the heat exchanger
Coil Diameter
Type: real number
This is the diameter of the heat exchanger coil
Unit: m
Default: 1.0
Coil Pitch
Type: real number
This is the center-to-center distance between coils
Unit: m
Default: 0.20
Trench Depth
Type: real number
This is the distance from the ground surface to the trench bottom
Unit: m
Default: 1.8
Trench Length
Type: real number
This is the total length of a single trench This assumes the heat exchanger runs the full length of the trench
Unit: m
Default: 10
Number of Trenches
Type: integer
This is the number of parallel trenches that has a heat exchanger, one per trench
Minimum: 1
Default: 1
Horizontal Spacing Between Pipes
Type: real number
This represents the average horizontal spacing between any two trenches for heat exchangers that have multiple trenches
Unit: m
Default: 2.0
Undisturbed Ground Temperature Model Type
Type: choice
(Site:GroundTemperature:Undisturbed:FiniteDifference, Site:GroundTemperature:Undisturbed:KusudaAchenbach or Site:GroundTemperature:Undisturbed:Xing)
Undisturbed Ground Temperature Model Name
Type: list of objects
(
SITE:GROUNDTEMPERATURE:UNDISTURBED:XING,
SITE:GROUNDTEMPERATURE:UNDISTURBED:KUSUDAACHENBACH or
SITE:GROUNDTEMPERATURE:UNDISTURBED:FINITEDIFFERENCE)
Maximum Length of Simulation
Type: real number
Unit: years