FAN:CONSTANTVOLUME
Constant volume fan that is intended to operate continuously based on a time schedule. This fan will not cycle on and off based on cooling/heating load or other control signals.
Name
Availability Schedule Name
Type: list of objects
(
SCHEDULE:YEAR,
SCHEDULE:FILE,
SCHEDULE:COMPACT,
EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE,
EXTERNALINTERFACE:SCHEDULE or
SCHEDULE:CONSTANT)
Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Fan Total Efficiency
Type: real number
Maximum: 1.0
Default: 0.7
Pressure Rise
Unit: Pa
Maximum Flow Rate
Unit: m3/s
Minimum: 0.0
Motor Efficiency
Type: real number
Maximum: 1.0
Default: 0.9
Motor In Airstream Fraction
Type: real number
0.0 means fan motor outside of air stream, 1.0 means motor inside of air stream
Minimum: 0.0
Maximum: 1.0
Default: 1.0
Air Inlet Node Name
Type: node
Air Outlet Node Name
Type: node
End-Use Subcategory
Type: alphanumeric
Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
Default: General