DEMANDMANAGER:VENTILATION
used for demand limiting Controller:OutdoorAir objects.
Name
Type: alphanumeric
Availability Schedule Name
Type: list of objects
(
SCHEDULE:COMPACT,
SCHEDULE:FILE,
SCHEDULE:YEAR,
SCHEDULE:CONSTANT,
EXTERNALINTERFACE:SCHEDULE or
EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE)
Availability schedule name for this demand manager. Schedule value > 0 means the demand manager is available. If this field is blank, the DR is always available.
Limit Control
Type: choice
(Off, FixedRate or ReductionRatio)
Minimum Limit Duration
Type: integer
If blank, duration defaults to the timestep
Unit: minutes
Fixed Rate
Type: real number
Used in case when Limit strategy is set to FixedRate
Unit: m3/s
Minimum: 0.0
Reduction Ratio
Type: real number
Used in case when Limit Control is set to ReductionRatio
Minimum: 0.0
Maximum: 1.0
Limit Step Change
Type: real number
Not yet implemented
Selection Control
Type: choice
(All, RotateMany or RotateOne)
Default: All
Rotation Duration
Type: integer
If blank, duration defaults to the timestep
Unit: minutes
Minimum: 0
Controller Outdoor Air 1 Name
Type: list of objects
( or
CONTROLLER:OUTDOORAIR)
Enter the name of a Controller:OutdoorAir object.
Controller Outdoor Air 2 Name
Type: list of objects
( or
CONTROLLER:OUTDOORAIR)
Controller Outdoor Air 3 Name
Type: list of objects
( or
CONTROLLER:OUTDOORAIR)
Controller Outdoor Air 4 Name
Type: list of objects
( or
CONTROLLER:OUTDOORAIR)
Controller Outdoor Air 5 Name
Type: list of objects
( or
CONTROLLER:OUTDOORAIR)
Controller Outdoor Air 6 Name
Type: list of objects
( or
CONTROLLER:OUTDOORAIR)
Controller Outdoor Air 7 Name
Type: list of objects
( or
CONTROLLER:OUTDOORAIR)
Controller Outdoor Air 8 Name
Type: list of objects
( or
CONTROLLER:OUTDOORAIR)
Controller Outdoor Air 9 Name
Type: list of objects
( or
CONTROLLER:OUTDOORAIR)
Controller Outdoor Air 10 Name
Type: list of objects
( or
CONTROLLER:OUTDOORAIR)