CURVE:FANPRESSURERISE

Special curve type with two independent variables. Input for the fan total pressure rise curve consists of the curve name, the four coefficients, and the maximum and minimum valid independent variable values. Optional inputs for the curve minimum and maximum may be used to limit the output of the performance curve. curve = C1*Qfan**2+C2*Qfan+C3*Qfan*(Psm-Po)**0.5+C4*(Psm-Po) Po assumed to be zero See InputOut Reference for curve details

Name
Type: alphanumeric

Coefficient1 C1
Type: real number

Coefficient2 C2
Type: real number

Coefficient3 C3
Type: real number

Coefficient4 C4
Type: real number

Minimum Value of Qfan
Type: real number
Unit: m3/s

Maximum Value of Qfan
Type: real number
Unit: m3/s

Minimum Value of Psm
Type: real number
Unit: Pa

Maximum Value of Psm
Type: real number
Unit: Pa

Minimum Curve Output
Type: real number
Specify the minimum value calculated by this curve object
Unit: Pa

Maximum Curve Output
Type: real number
Specify the maximum value calculated by this curve object
Unit: Pa