CURVE:CHILLERPARTLOADWITHLIFT
This chiller part-load performance curve has three independent variables. Input consists of the curve name, the twelve coefficients, and the maximum and minimum valid independent variable values. Optional inputs for the curve minimum and maximum may be used to limit the output of the performance curve. curve = C1 + C2*x + C3*x**2 + C4*y + C5*y**2 + C6*x*y + C7*x**3 + C8*y**3 + C9*x**2*y + C10*x*y**2 + C11*x**2*y**2 + C12*z*y**3 x = dT* = normalized fractional Lift = dT / dTref y = PLR = part load ratio (cooling load/steady state capacity) z = Tdev* = normalized Tdev = Tdev / dTref Where: dT = Lift = Leaving Condenser Water Temperature - Leaving Chilled Water Temperature dTref = dT at the reference condition Tdev = Leaving Chilled Water Temperature - Reference Chilled Water Temperature
Name
Type: alphanumeric
Coefficient1 C1
Type: real number
Coefficient2 C2
Type: real number
Coefficient3 C3
Type: real number
Coefficient4 C4
Type: real number
Coefficient5 C5
Type: real number
Coefficient6 C6
Type: real number
Coefficient7 C7
Type: real number
Coefficient8 C8
Type: real number
Coefficient9 C9
Type: real number
Coefficient10 C10
Type: real number
Coefficient11 C11
Type: real number
Coefficient12 C12
Type: real number
Minimum Value of x
Type: real number
Maximum Value of x
Type: real number
Minimum Value of y
Type: real number
Maximum Value of y
Type: real number
Minimum Value of z
Type: real number
Maximum Value of z
Type: real number
Minimum Curve Output
Type: real number
Specify the minimum value calculated by this curve object
Maximum Curve Output
Type: real number
Specify the maximum value calculated by this curve object
Input Unit Type for x
Type: choice
( or Dimensionless)
Default: Dimensionless
Input Unit Type for y
Type: choice
( or Dimensionless)
Default: Dimensionless
Input Unit Type for z
Type: choice
( or Dimensionless)
Default: Dimensionless
Output Unit Type
Type: choice
( or Dimensionless)
Default: Dimensionless