AIRLOOPHVAC:UNITARYHEATPUMP:AIRTOAIR

Unitary heat pump system, heating and cooling, single-speed with supply fan, direct expansion (DX) cooling coil, DX heating coil (air-to-air heat pump), and supplemental heating coil (gas, electric, hot water, or steam).

Name
Type: alphanumeric

Availability Schedule Name
Type: list of objects (SCHEDULE:YEAR, SCHEDULE:FILE, SCHEDULE:COMPACT, EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE, EXTERNALINTERFACE:SCHEDULE or SCHEDULE:CONSTANT)
Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available. A schedule value greater than zero (usually 1 is used) indicates that the unit is available to operate as needed. A value less than or equal to zero (usually zero is used) denotes that the unit must be off.

Air Inlet Node Name
Type: node

Air Outlet Node Name
Type: node

Cooling Supply Air Flow Rate
Type: real number
Must be less than or equal to the fan's maximum flow rate.
Unit: m3/s

Heating Supply Air Flow Rate
Type: real number
Must be less than or equal to the fan's maximum flow rate.
Unit: m3/s

No Load Supply Air Flow Rate
Type: real number
Must be less than or equal to the fan's maximum flow rate. Only used when fan operating mode is continuous (disregarded for cycling fan mode). This air flow rate is used when no heating or cooling is required (i.e., the DX coil compressor and supplemental heating coil are off). If this field is left blank or zero, the supply air flow rate from the previous on cycle (either cooling or heating) is used.
Unit: m3/s
Minimum: 0.0

Controlling Zone or Thermostat Location
Type: list of objects ( or ZONE)

Supply Air Fan Object Type
Type: choice (Fan:OnOff or Fan:ConstantVolume)
Fan:ConstantVolume only works with continuous fan operating mode (i.e. fan operating mode schedule values are greater than 0 or the fan operating mode schedule name field is left blank).

Supply Air Fan Name
Type: list of objects (FAN:CONSTANTVOLUME or FAN:ONOFF)
Needs to match in the fan object

Heating Coil Object Type
Type: choice (Coil:Heating:DX:SingleSpeed, Coil:Heating:DX:VariableSpeed or CoilSystem:IntegratedHeatPump:AirSource)
Only works with Coil:Heating:DX:SingleSpeed or Coil:Heating:DX:VariableSpeed or CoilSystem:IntegratedHeatPump:AirSource

Heating Coil Name
Type: list of objects (COIL:HEATING:DX:SINGLESPEED or COIL:HEATING:DX:VARIABLEREFRIGERANTFLOW)
Needs to match in the DX heating coil object

Cooling Coil Object Type
Type: choice (Coil:Cooling:DX:SingleSpeed, Coil:Cooling:DX:VariableSpeed, CoilSystem:Cooling:DX:HeatExchangerAssisted or CoilSystem:IntegratedHeatPump:AirSource)
Only works with Coil:Cooling:DX:SingleSpeed or CoilSystem:Cooling:DX:HeatExchangerAssisted or Coil:Cooling:DX:VariableSpeed or CoilSystem:IntegratedHeatPump:AirSource

Cooling Coil Name
Type: list of objects (COILSYSTEM:COOLING:DX:HEATEXCHANGERASSISTED, COIL:COOLING:DX:SINGLESPEED:THERMALSTORAGE or COIL:COOLING:DX:SINGLESPEED)
Needs to match in the DX cooling coil object

Supplemental Heating Coil Object Type
Type: choice (Coil:Heating:Fuel, Coil:Heating:Electric, Coil:Heating:Water or Coil:Heating:Steam)
Works with gas, electric, hot water and steam heating coils

Supplemental Heating Coil Name
Type: list of objects (COIL:HEATING:FUEL, COIL:HEATING:ELECTRIC, COIL:HEATING:WATER or COIL:HEATING:STEAM)
Needs to match in the supplemental heating coil object

Maximum Supply Air Temperature from Supplemental Heater
Type: real number
Unit: C

Maximum Outdoor Dry-Bulb Temperature for Supplemental Heater Operation
Type: real number
Unit: C
Maximum: 21.0
Default: 21.0

Fan Placement
Type: choice (BlowThrough or DrawThrough)
Default: BlowThrough

Supply Air Fan Operating Mode Schedule Name
Type: list of objects (SCHEDULE:YEAR, SCHEDULE:FILE, SCHEDULE:COMPACT, EXTERNALINTERFACE:FUNCTIONALMOCKUPUNITIMPORT:TO:SCHEDULE, EXTERNALINTERFACE:SCHEDULE or SCHEDULE:CONSTANT)
A fan operating mode schedule value of 0 indicates cycling fan mode (supply air fan cycles on and off in tandem with the cooling or heating coil). Any other schedule value indicates continuous fan mode (supply air fan operates continuously regardless of cooling or heating coil operation). Leaving this schedule name blank will default to cycling fan mode for the entire simulation period.

Dehumidification Control Type
Type: choice (None, Multimode or CoolReheat)
None = meet sensible load only Multimode = activate enhanced dehumidification mode as needed and meet sensible load. Valid only with cooling coil type CoilSystem:Cooling:DX:HeatExchangerAssisted. This control mode allows the heat exchanger to be turned on and off based on the zone dehumidification requirements. A ZoneControl:Humidistat object is also required. CoolReheat = cool beyond the dry-bulb setpoint. as required to meet the humidity setpoint. Valid with all cooling coil types. When a heat exchanger assisted Cooling coil is used, the heat exchanger is locked on at all times. A ZoneControl:Humidistat object is also required.
Default: None