AIRFLOWNETWORK:DISTRIBUTION:COMPONENT:RELIEFAIRFLOW
This object allows variation of air flow rate to perform pressure.
Name
Outdoor Air Mixer Name
Air Mass Flow Coefficient When No Outdoor Air Flow at Reference Conditions
Type: real number
Enter the air mass flow coefficient at the conditions defined in the Reference Crack Conditions object. Defined at 1 Pa pressure difference. Enter the coefficient used in the following equation: Mass Flow Rate = Air Mass Flow Coefficient * (dP)^Air Mass Flow Exponent. Used only when no outdoor air flow rate.
Unit: kg/s
Air Mass Flow Exponent When No Outdoor Air Flow
Type: real number
Enter the exponent used in the following equation: Mass Flow Rate = Air Mass Flow Coefficient * (dP)^Air Mass Flow Exponent. Used only when no outdoor air flow rate.
Unit: dimensionless
Minimum: 0.5
Maximum: 1.0
Default: 0.65
Reference Crack Conditions
Type: list of objects
( or
AIRFLOWNETWORK:MULTIZONE:REFERENCECRACKCONDITIONS)
Select a AirflowNetwork:MultiZone:ReferenceCrackConditions name associated with the air mass flow coefficient entered above.