AIRFLOWNETWORK:DISTRIBUTION:COMPONENT:DUCT
This object defines the relationship between pressure and air flow through the duct.
Name
Type: alphanumeric
Enter a unique name for this object.
Duct Length
Type: real number
Enter the length of the duct.
Unit: m
Hydraulic Diameter
Type: real number
Enter the hydraulic diameter of the duct. Hydraulic diameter is defined as 4 multiplied by cross section area divided by perimeter
Unit: m
Cross Section Area
Type: real number
Enter the cross section area of the duct.
Unit: m2
Surface Roughness
Type: real number
Enter the inside surface roughness of the duct.
Unit: m
Default: 0.0009
Coefficient for Local Dynamic Loss Due to Fitting
Type: real number
Enter the coefficient used to calculate dynamic losses of fittings (e.g. elbows).
Unit: dimensionless
Minimum: 0.0
Default: 0.0
Heat Transmittance Coefficient (U-Factor) for Duct Wall Construction
Type: real number
Conduction only Default value of 0.943 is equivalent to 1.06 m2-K/W (R6) duct insulation.
Unit: W/m2-K
Default: 0.943
Overall Moisture Transmittance Coefficient from Air to Air
Type: real number
Enter the overall moisture transmittance coefficient including moisture film coefficients at both surfaces.
Unit: kg/m2
Default: 0.001
Outside Convection Coefficient
Type: real number
Optional. convection coefficient calculated automatically, unless specified
Unit: W/m2-K
Inside Convection Coefficient
Type: real number
Optional. convection coefficient calculated automatically, unless specified
Unit: W/m2-K